Fast and effective:
LV-Text Generator
SHEV module control unit MZ3-..A-..RG-..LG-..MK
Article No.: 1111136
1 ATs englische Version
________________________________________________________________________________
01.01 01 Control systems
________________________________________________________________________________
01.01.01 24V SHE and Ventilation
________________________________________________________________________________
01.01.01.0001 SHEV module control unit MZ3-..A-..RG-..LG-..MK
________________________________________________________________________________
Self-monitoring modular SHE BUS system.
Energy supply certified according to EN 12101-10 and functions certified
according to prEN 12101-9: compliant with all essential characteristics based
on VdS tests.
[16A] [32A] [...] current output, buil din:
- ... SHE groups
- ... RWA groups
- ... Venting groups
- ... Motor circle max [8A] [14A] [20A] current output
- ... 230/400V ... kW load outputs
Installation in areas according to requirements, with the following additional
functions:
-... Smoke extraction depending on wind direction
-... Ventilation depending on wind direction
-... Primary circuit for ... shading groups
-... Wind speed threshold values
-... Fire alarm system lines with activation via N/C or N/O contact
- ... SHE group, fault = trigger
-... In ventilation groups with stroke limitation
-... master group for central function of ventilation
Depending on design and configuration for the connection of
- 24V/DC SHE safety drives and 24V/DC ventilation drives
- SHE button, type RBH/..
- Automatic indicators, type MSD & UTD 523
- Ventilation buttons, type LT/.., LTA/.. with and without "Flap Open" and
"Wind/Rain" display
- Temperature sensors, type TS/..
- Rain indicator RM/2 24V and Wind/Rain indicator WRM/2 24V
The MZ3 ESSmatic functions enable the interface solutions to LON, KNX and the
coupling of MZ3 centre via CAN and LON bus.
Silver friendly design and signal system
and storing of events and conditions.
7-segment display for messages and configuration.
All functions and components are preconfigured and ready for installation:
- Sheet-metal housing (RAL 7035)
- Protection type IP42
- with padlock
- Emergency power battery and charging unit
With monitoring functions of the
- monitoring the indicator circuit (automatic indicator and SHE control panel)
- monitoring the motor wiring
- grid and battery monitoring
- with fault indicator at the switchboard and SHE control panels
- Data bus line
Integrated maintenance timer for the protection of the operational readiness.
Maintenance interval 12 months.
Resetting via service port software and maintenance credit.
MENGE: .......... EINHEIT: pcs EP: ............ GP: ............